Variable Frequency Drives

Variable Frequency Drives

Siemens
Item ID: BT300-010X2-01X
  • Over-voltage and under-voltage trip limit
  • Ground fault protection
  • Mains supervision
  • Motor phase supervision
  • Over-current protection
  • Unit over-temperature protection
  • Motor overload and underload protection
  • Motor stall protection
  • Short-circuit protection of +24V and +10V reference voltages
PWM frequency 1.5 to 10 kHz
Analog Output Signal Selectable voltage or current; resolution 0.1%; accuracy +/- 1%; DC 0...10 V;DC 0...20 mA
Degree of Protection NEMA Type 1
Relay Outputs 2 Form C, 1 Normally Open / Number: 2 / Switching Voltage: 24 Vdc / 8A; 250 Vac / 8A; 125 Vdc / 0.4A
Analog Input Signal: Selectable voltage or current; resolution 0.1%; accuracy +/- 1%; DC 0...10 V;DC 4...20 mA / Number: 2
Communication RS485 and Ethernet; Modbus RTU, Modbus TCP; BACnet MSTP, BACnet IP; Metasys N2
Analog outputs, number 1
Digital Input Signal: 0 to 5V = "0"; 15 to 30V = "1" / Number: 6
Brand Siemens
Certifications UL 508C, UL, CE, cUL, RoHS compliant
Country of Origin Finland
Hertz 50/60
Housing Material UL Type 1
Operating Temperature Range 14° F (-10°C) (no frost) to 104°F (40°C); up to 122°F (50°C) with de-rating; 0 to 95% RH, non-condensing, non-corrosive
Operating Voltage (VAC) 208/240 V
Output Output current: 31 A / Frequency: 0 to 320 Hz / Power: 10HP, 7.5 kW
Overload Protection Capacity: 1.1 × Nominal rated output current 110% for 1 minute/10 minutes
UPC 804766023026